SeaLand 3100 Spezifikationen Seite 37

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 51
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 36
APT3100 Smart Pressure Transmitter Operation Manual M3100-EO1G
33
Duon System Co.,Ltd.
4.7.6 Power Supply Voltage and Load Resistance
When configuring the loop, make sure that the external load resistance is within the range in the
figure below. Since the voltage of transmitter terminal input is same as follows.
z General Standard : 11.9 to 45 Vdc
z Hart Communication : 17.4 to 45 Vdc
z KOSHA Explosionproof : 11.9 to 45 Vdc
z CSA Explosionproof : 17.4 to 42 Vdc max.
And maximum loop current is 24mA, Load resistance R:
R = (E-11.9) / 0.022 (E = Power Supply Voltage)
[Note] In case of an intrinsically safe transmitter, external load resistance includes safety barrier
resistance.
Seitenansicht 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 50 51

Kommentare zu diesen Handbüchern

Keine Kommentare