APT3100 Smart Pressure Transmitter Operation Manual M3100-EO1G
12
Duon System Co.,Ltd.
z Nonsparking Equipment for class I, Zone 2 : Ex nA IIC T4
z Enclosure : Type 4X, IP66
z Ambient Temperature : -20 to 60 °C
z Supply Voltage : 42V dc max.
z Output Signal : 4 to 20mA + HART®
z Electrical Connection : 1/2” – 14 npt Female
z List of standards that product compiles with,
z specifically E60079-1 end E60079-15.
z The warning: “WARNING-EXPOLSION HAZARD-SUBSTITUTION OF
z COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2” or equivalent.
Note 2. Installation
z All wirings have to be installed by the final revision of Canadian Electrical Code.
z Input equipment of cable should be certified by explosionproof and be adjusted to using
conditions.
z Wire connection that is no use has blocked by available plugs.
z All screws of cable tube have to be set the 5 teeth.
z Method of cable connection has to be followed by Class I, Division 1 in spite of its length.
z All cable tubes have to be sealed with 50 cm from housing.
z Installation in Division 2 zone does not need to be sealed.
z In assembly of sensor module and housing, over 7 screws have to be set the teeth and be
fixed in order not to spin.
Note 3. Operation
z Be cautious of the CAUTION attached to transmitter.
CAUTION IN EXPLOSIVE ATMOSHERE DO NOT OPEN WHILE ENERGIZED
z Wait one minute after power-disconnection, before opening the enclosure.
z Take care not to generate mechanical spark when access to the instrument and
peripheral devices in hazardous location.
Note 4. Maintenance and Repair
z The instrument modification or parts replacement by other than authorized
representative of DUON System is prohibited and will void CSA Explosionprooof /
Flameproof.
2-10-4. FM Certification
HAZARDOUS LOCATION ELECTRICAL EQUIPMENT
APT3100-abclgjkm. Pressure Transmitters.
APT3100-abcdefgijklm. Pressure Transmitters.
APT3100-abcdfghiklm. Pressure Transmitters.
XP/I/1/ABCD/T6 Ta = 60;