APT3100 Smart Pressure Transmitter Operation Manual M3100-EO1G
6
Duon System Co.,Ltd.
Chapter 2 Handling Cautions
This chapter consists of cautions for transmitter handling and storage, selection of installation locations,
insulation and explosion structure, etc.
[Quick Reference Manual]
Step Job Job Details Instrument
1 Unpacking - Unpack transmitter packing
2
Model and
Specifications
Check
- Make sure whether the delivered transmitter is same
as options attached on its nameplate
3 Storage
- Places not exposed to water, non-vibration and non-
impact area
- Ambient temperature 25 deg C and relative humidity
65% RH
4
Calibration on a
Calibration Room
- Configuration of Range, Zero/Span, Unit, Tag,
Damping Time, Transfer Function, DA Trim and other
parameters
- HHT
- Pressure
Source
(requested)
- Galvanometer
5
Installation
Locations
- Where ambient temperature is not fluctuated
- Where corrosion happens by chemical materials, etc.
- Where vibration and impact is not severe
- Where non-explosion area is matched on
explosionproof regulations
- Where maintenance is very easy
(Engineering)
6
Mechanical
Considerations
- Where transmitter can be handled easily
- Be cautious not leaking the pressure.
(Engineering)
7
Electrical
Considerations
- Connect 24 Vdc
(Power Supply is 11.9 Vdc – 45 Vdc)
- For HART communication, total resistance on
transmitter terminal loop should be 250 – 550 Ohm.
(Engineering)
8
Mounting and
Installation
- For mounting transmitter, an appropriate bracket
should be used.
- Transmitter should be fixed well against swing.
(Mounting and
Installation)
9
Calibration on
Spot
- Sensor Zero Trim has to be done after ten seconds,
namely, differential pressure become zero and
stabilized.
- Make sure that PV value of transmitter is zero and
current is 4 mA.
HHT or
Zero/Span
button
10 Pressure
- Do not apply the regulated differential and line
pressure.
- Close equalizing valve of 3 valve manifold, Then,
open stop valve on high and low side slowly and
simultaneously.
(Applying
pressure)
11 Operation - Make sure whether transmitter operates well or not Eye or HHT